Deterministic NFPA 10 (2022) Rule Engine

NFPA 10 Hydrostatic Test & 6-Year Maintenance Calculator

Select a rechargeable extinguisher's agent type and cylinder manufacture year (or last hydrostatic test year) to estimate 6-year internal examination and 5-year or 12-year hydrostatic test schedules under NFPA 10 (2022).

Worked Calculation Examples by Extinguisher Type

Compare how different extinguishing agents, shell materials, and disposable units follow completely different NFPA 10 (2022) schedules:

Extinguisher ExampleAnchor Date6-Year / Agent ServiceHydrostatic Test YearsRule / Note
10 lb ABC Dry Chemical
Stored-pressure, mild steel
Mfg 2020
No prior hydro
2026, 2038 2032, 2044
(every 12 yrs)
2032 hydro supersedes & resets the 6-yr clock (NFPA 10 7.3.6).
15 lb CO2
High-pressure cylinder
Last Hydro 2021 Not required 2026, 2031, 2036
(every 5 yrs)
5-yr hydro per Table 8.3.1 & OSHA Table L-1; no 6-yr teardown.
6L Class K Wet Chemical
Commercial kitchen
Mfg 2023
No prior hydro
Not required 2028, 2033, 2038
(every 5 yrs)
5-yr hydro interval per NFPA 10 Table 8.3.1.
2.5 gal AFFF / FFFP Foam
Stored-pressure foam
Mfg 2022
No prior hydro
3-yr agent replace: 2025, 2028 2027, 2032, 2037
(every 5 yrs)
Requires 3-yr pre-mixed foam replacement (7.8.1.3) + 5-yr hydro.
Disposable ABC Dry Chem
Nonrechargeable plastic/metal
Mfg 2018 Exempt from 6-yr Retire in 2030
(12-yr max life)
Do NOT hydro-test; remove from service at 12 yrs (NFPA 10 7.3.6.2).

Manufacture Date vs. Last Test Date: Which Anchor to Enter?

  • Cylinder Manufacture Year (always required): Stamped into the metal cylinder collar/bottom (e.g., 2020 or 20) or printed on the UL nameplate. Used as the baseline for brand-new cylinders that have never been hydro-tested.
  • Last Hydrostatic Test Year (overrides Mfg Year for hydro): Stamped onto high-pressure shells (CO2) or affixed on a foil hydrostatic label on low-pressure shells (ABC/Class K). When entered, the next 5-yr or 12-yr hydro test counts from this year — and also resets the 6-year internal clock.
  • Last 6-Year Maintenance Year (does NOT reset 12-yr hydro): Recorded on a metallic verification label attached to the back of the cylinder. Entering an off-cycle recharge/teardown shifts the next 6-year check, while the 12-year hydrostatic deadline stays anchored to Manufacture Year or Last Hydro Year (and resets the 6-year clock again once hydro is performed).

Calculation Assumptions & Scope Limits

  • Serviceable rechargeable cylinders only: Output assumes the shell is rechargeable and passes visual/annual inspection.
  • Calendar-year rule (NFPA 10 8.3.1): Hydrostatic retests are scheduled by calendar year of the required interval unless your local AHJ or DOT cylinder specification enforces an exact month/year cutoff.
  • Nonrechargeable (disposable) units: Exempt from 6-year teardown and hydrostatic retesting — retire at 12 years from manufacture (NFPA 10 7.3.6.2 & OSHA 1910.157(e)(4)).
  • Stainless-steel dry-chemical shells: Stored-pressure dry-chemical extinguishers with stainless-steel shells require a 5-year hydro interval, not 12 years (NFPA 10 Table 8.3.1).
  • Cartridge-operated dry chemical: Follow annual internal examination rules rather than 6-year teardowns.
  • Immediate condemnation (NFPA 10 Section 8.4): Never wait for a scheduled year if a cylinder shows deep corrosion/pitting, fire or heat damage, soldered/welded repairs, or damaged threads — condemn and remove from service immediately.

NFPA 10 (2022) Test Interval Quick Reference Table

Extinguisher Agent6-Year Internal MaintenanceHydrostatic Test IntervalNFPA 10 / OSHA Reference
ABC Dry Chemical (Stored-Pressure, Mild Steel / Alum / Brass) Every 6 years Every 12 years NFPA 10 (2022) 7.3.6 (6-yr internal) & Table 8.3.1 (12-yr hydro, mild steel/alum/brass)
BC Dry Chemical (Stored-Pressure, Mild Steel / Alum / Brass) Every 6 years Every 12 years NFPA 10 (2022) 7.3.6 (6-yr internal) & Table 8.3.1 (12-yr hydro, mild steel/alum/brass)
Dry Chemical — Stainless-Steel Shell (Stored-Pressure) Not required Every 5 years NFPA 10 (2022) Table 8.3.1 & OSHA 1910.157 Table L-1 (5-yr hydro for stainless-steel shells)
Nonrechargeable / Disposable Dry Chemical (12-yr Retire) Not required Every 12 years NFPA 10 (2022) 7.3.6.2 & OSHA 1910.157(e)(4) (12-yr mandatory retirement; no 6-yr or hydro)
Cartridge-Operated Dry Chemical (Annual Internal Exam) Not required Every 12 years NFPA 10 (2022) Table 7.3.3.1 (annual internal) & Table 8.3.1 (12-yr mild steel / 5-yr stainless hydro)
Clean Agent (Halotron / FE-36, Rechargeable) Every 6 years Every 12 years NFPA 10 (2022) 7.3.6 (6-yr internal) & Table 8.3.1 (12-yr hydro)
Carbon Dioxide (CO2) Not required Every 5 years NFPA 10 (2022) Table 8.3.1 & OSHA 1910.157 Table L-1 (5-yr hydro; no 6-yr teardown)
Pressurized Water / Water Mist Not required Every 5 years NFPA 10 (2022) Table 8.3.1 (5-yr hydro; verify loaded-stream/antifreeze annual internal rules)
Class K Wet Chemical (Kitchen) Not required Every 5 years NFPA 10 (2022) Table 8.3.1 (5-yr hydro; no 6-yr teardown)
Foam (AFFF / FFFP / SFFF) Not required Every 5 years NFPA 10 (2022) Table 8.3.1 (5-yr hydro) & Table 7.3.3.1 / 7.8.1.3 (3-yr agent replacement)
Regulatory Editions, Official Sources & Local AHJ Scope: Guidance and interval calculations on this page reference NFPA 10 (2022 Edition) (nfpa.org) and federal OSHA 29 CFR 1910.157 for U.S. general industry workplaces (osha.gov). Note that OSHA 1910.157(b) contains partial/total exemptions when an employer's written emergency action plan mandates total evacuation without employee extinguisher use, while states, cities, and insurance carriers frequently adopt earlier or amended NFPA 10 editions (such as 2018 or 2022) via IFC/NFPA 1. FireTagLog is a recordkeeping and calculation assistant — final compliance verification, tag format approval, and licensed maintenance remain the responsibility of your certified technician and local Authority Having Jurisdiction (AHJ).