NFPA 10 (2022 Edition) & OSHA 29 CFR 1910.157 Reference

NFPA 10 & OSHA 29 CFR 1910.157 Inspection Requirements

Where portable fire extinguishers are provided for commercial workplace use, NFPA 10 (2022) and OSHA 29 CFR 1910.157 govern four distinct inspection, maintenance, and testing cycles — along with specific scope exemptions and condemnation triggers.

Master Comparison: Monthly, Annual, Internal Maintenance & Hydrostatic Testing

Compliance Cycle Interval NFPA 10 (2022) & OSHA Clauses Who Performs It Record & Retention Key Exceptions
Monthly Visual Inspection Every ~30 days NFPA 10 7.2 / 7.2.4
OSHA 1910.157(e)(2)
Trained in-house staff or facility manager Month, year & initials kept >= 12 mos (NFPA 10 7.2.4; electronic ok per 7.2.4.2) More frequent checks where severe hazards, vibration, or tampering exist (7.2.1.3)
Annual Maintenance Every 12 months NFPA 10 7.3.2
OSHA 1910.157(e)(3)
Certified / licensed fire protection technician (7.1.2) Service tag + date record retained 1 yr after last entry or life of the shell, whichever is less (OSHA (e)(3)) Stored-pressure units do not need annual internal exam unless indicated externally
6-Year Internal Examination Every 6 years NFPA 10 7.3.6
OSHA 1910.157(e)(4)
Certified fire protection technician w/ recharge gear Metallic verification label on shell + service record Applies to rechargeable stored-pressure 12-yr hydro units only; disposable units exempt (retire at 12 yrs); cartridge units follow annual internal exam; foam needs 3-yr agent replace (7.8.1.3)
Hydrostatic Pressure Test Every 5 or 12 years NFPA 10 Table 8.3.1 & 8.4
OSHA 1910.157 Table L-1
DOT / certified hydrostatic testing facility Stamp on high-pressure shell or foil test label on low-pressure shell 5-yr: CO2, water, Class K, foam, stainless-steel dry chem. 12-yr: mild steel/alum/brass dry chem & clean agent. Immediate condemnation for corrosion/pitting/fire damage (8.4)

Scope & Applicability: OSHA 29 CFR 1910.157 vs. NFPA 10 (2022)

Federal OSHA 29 CFR 1910.157 applies to U.S. general industry employers who provide portable fire extinguishers for employee use. Under 1910.157(b)(1)–(2), if an employer maintains a written Emergency Action Plan (1910.38) and Fire Prevention Plan (1910.39) requiring immediate, total workplace evacuation — and extinguishers are not intended for employee use — certain federal provisions of 1910.157 are exempt.

However, state and municipal fire codes (such as the International Fire Code or NFPA 1) and commercial property insurers typically still require buildings to install and maintain portable extinguishers under NFPA 10 regardless of federal OSHA evacuation policies. Always verify which NFPA 10 edition (e.g., 2018 or 2022) and licensing rules your local Authority Having Jurisdiction (AHJ) enforces.

Step-by-Step Monthly Inspection Procedure (NFPA 10 7.2.2)

  1. Accessible & Unobstructed: Mounted in designated location, visible signage, zero blockages. (NFPA 10 7.2.2(1)-(2))
  2. Pressure Gauge in Operable Range: Needle in green zone (or verified full weight for CO2 cylinders). (NFPA 10 7.2.2(4))
  3. Pull Pin & Tamper Seal Intact: Safety pin seated and tamper indicator unbroken. (NFPA 10 7.2.2(3))
  4. Hose, Nozzle & Horn Clear: No cracks, splits, blockages, or loose fittings. (NFPA 10 7.2.2(5))
  5. Cylinder & Nameplate Undamaged: No corrosion, leakage, dents, or illegible UL/FM nameplate. (NFPA 10 7.2.2(6))
  6. Operating Instructions Facing Outward: Label legible and readable without rotating extinguisher. (NFPA 10 7.2.2(7))

For CO2 or cartridge-operated units without a pressure gauge, verify fullness by hefting or weighing against the stamped gross weight and confirm the tamper seal is intact.

Common Field Deficiencies & Required Actions

Observed DefectClauseImmediate Required Action
Blocked by pallets / doors 7.2.2(2) Clear obstruction immediately; mark location signage clearly.
Gauge needle in red (low or overcharged) 7.2.2(5) / 7.2.3 Remove from service, place charged spare, send for certified recharge/service.
Broken tamper seal or missing pull pin 7.2.2(7) / 7.2.3 Assume partial discharge or tampering; remove and schedule certified inspection/recharge.
Cracked hose, clogged nozzle, or loose horn 7.2.2(4) Tag out of service; certified tech must replace damaged hose/nozzle assembly.
Deep rust pitting, fire damage, welds, or dents 8.4.1 Condemn immediately — do NOT hydro-test or return to service.
Missing/unreadable label or expired annual tag 7.2.2(3) / 7.3.2 Schedule certified annual maintenance immediately; replace unit if rating label is illegible.

6-Year Internal Maintenance Details & Exceptions

Under NFPA 10 (2022) Section 7.3.6 and OSHA 1910.157(e)(4), rechargeable stored-pressure extinguishers requiring a 12-year hydrostatic test (such as standard ABC/BC dry chemical and Halotron/FE-36 clean agent) must be completely discharged, internally examined, fitted with replacement O-rings/valve stems as needed, and recharged every 6 years.

When a unit is recharged or hydrostatically tested, the 6-year interval resets from that date. Exceptions: Nonrechargeable (disposable) dry-chemical units are exempt and must be retired at 12 years from manufacture (7.3.6.2); cartridge-operated dry-chemical extinguishers undergo annual internal inspection instead.

Run 6-Yr & 12-Yr Calculator ›

Hydrostatic Testing (5-Yr vs. 12-Yr) & Record Tools

Under NFPA 10 (2022) Table 8.3.1 and OSHA 1910.157 Table L-1: CO2, pressurized water/water mist, Class K wet chemical, AFFF/FFFP foam (which also needs 3-year agent replacement per 7.8.1.3), and dry-chemical units with stainless-steel shells require hydrostatic testing every 5 years. Rechargeable mild-steel, aluminum, or brass dry-chemical and clean-agent shells require testing every 12 years.

NFPA 10 (2026 Edition) Updates vs. Local AHJ Adoption

While FireTagLog's interactive calculators default to NFPA 10 (2022 Edition) and federal OSHA 29 CFR 1910.157 intervals (still the most widely enforced baseline across U.S. jurisdictions), NFPA has published the 2026 Edition of NFPA 10 with four notable updates:

  • Electronic monitoring & performance-based inspections (Chapter 7): Formally recognizes approved electronic monitoring systems and AHJ-approved performance-based inspection programs to supplement or adjust traditional manual monthly checks (including hefting checks where continuous monitoring is deployed).
  • Unified foam terminology: Consolidates legacy AFFF, FFFP, and fluorine-free SFFF references under a unified foam extinguisher definition as facilities transition away from fluorinated foams.
  • Delicate electronic equipment guidance (Chapter 5 Annex A): Expands examples clarifying when clean-agent extinguishers are warranted around sensitive electronics.
  • Condemned non-DOT/TC cylinder disposal (Chapter 8): Adds explicit disposal rules for condemned cylinders that fall outside standard DOT / Transport Canada specifications.

Important adoption rule: A newly published NFPA edition is not legally binding in a building until adopted by your state/municipal fire code (IFC / NFPA 1) or local Authority Having Jurisdiction (AHJ). Federal OSHA 29 CFR 1910.157 remains separate federal workplace law.

Regulatory Editions, Official Sources & Local AHJ Scope: Guidance and interval calculations on this page reference NFPA 10 (2022 Edition) (nfpa.org) and federal OSHA 29 CFR 1910.157 for U.S. general industry workplaces (osha.gov). Note that OSHA 1910.157(b) contains partial/total exemptions when an employer's written emergency action plan mandates total evacuation without employee extinguisher use, while states, cities, and insurance carriers frequently adopt earlier or amended NFPA 10 editions (such as 2018 or 2022) via IFC/NFPA 1. FireTagLog is a recordkeeping and calculation assistant — final compliance verification, tag format approval, and licensed maintenance remain the responsibility of your certified technician and local Authority Having Jurisdiction (AHJ).